Fronius CL 36.0 Central Inverter 36kW Grid Tied 3-phase WYE 277/240VAC
Free Shipping does not apply to Fronius CL Inverters
Unique System design with the Fronius MIXTM concept
Nine power modules operate in the Fronius CL 36.0 accomplishing something great together. This combination of several power modules has many advantages: maximum earnings in partial load ranges, high system stability, long service life and easy servicing.
Highest partial load efficiency.
Nine identical power modules divide up the work in the MIX™ concept. The individual power racks are turned off and on automatically depending on the insolation power. This ensures that the load is optimized and yield is always at maximum – even while raining, when cloudy or at dusk.
Unsurpassed reliability.
The Fronius CL creates a redundant system because it integrates several smaller power modules that work together. If one power module should fail, the others simply take up the slack. In comparison: when the power module fails in monolithic systems, the entire system stops operating and this leads to considerable loss of earnings. The Fronius MIX™ concept ensures that the inverter remains in operation even when there is a defect in a power module and this helps to lock in your earnings.
Long service life.
The control unit automatically calculates which power racks and how many will be turned on and off in partial load operation using the respective operating hours of the power modules. This helps to equalize the work load on the PC boards. This also decreases the operating hours of the individual power modules thus increasing the service life of the inverter.
Fast service option.
When service is required, power modules can be removed and replaced easily via the plug & play principle and drawer design. This ensures the highest serviceability and the fastest reaction times on the market.
| |
| |
Fronius CL 33.3 Delta |
Fronius CL 36.0 WYE277 |
| INPUT DATA |
|
|
| Recommended PV-Power |
28.3 - 39.0 kWp |
30.6 - 42.1 kWp |
| MPPT-Voltage Range |
230 ... 500 V |
230 ... 500 V |
Max. Input Voltage (at 1000 W/m²
14°F in open circuit operation) |
600 V |
600 V |
| Nominal Input Voltage |
390V |
390V |
| Nominal Input Current |
90.8 A |
98.2A |
| Max. usable Input Current |
154.0 A |
166.5 A |
| DC Startup Voltage |
245 V |
245 V |
| Admissible Conductor Size (DC) |
350 MCM |
350 MCM |
| No. of DC Input Terminals |
2X M12 (1/2") lug per hole |
2X M12 (1/2") lug per hole |
| No. of MPP Trackers |
1 |
1 |
| OUTPUT DATA |
|
|
| Nominal output power (PAC nom) |
33300 W |
36000 W |
| Max. continuous output power (40°C) 208 V |
33300 W |
n/a |
| Max. continuous output power (40°C) 240 V |
33300 W |
n/a |
| Max. continuous output power (40°C) 277 V |
n/a |
36000 W |
| Nominal AC output voltage |
208/240 V |
277 V |
| Operating AC voltage range default 208 V |
183-229V |
n/a |
| 240 V |
211-264V |
n/a |
| 277 V |
n/a |
244-305V |
| Nominal output current 208 V |
92.4A |
n/a |
| 240 V |
80.1A |
n/a |
| 277 V |
n/a |
43.3A |
| Number of phases |
3 |
3 |
| Admissible conductor size (AC) |
350 MCM |
350 MCM |
| No. of AC Terminals |
2X M10 (7/16") lug per hole |
2x M10 lug per pole |
| Max. continuous utility backfeed current |
0 A |
0 A |
| Nominal output frequency |
60 Hz |
60 Hz |
| Operating frequency range |
59.3 - 60.5 Hz |
59.3 - 60.5 Hz |
| Total harmonic distortion |
< 3 % |
< 3 % |
| Power Factor |
1 |
1 |
| GENERAL DATA |
|
|
| Max. Efficiency |
95.9 % |
95.9 % |
| CEC Efficiency 208 V |
94.5 % |
n/a |
| 240 V |
95.0% |
n/a |
| 277 V |
n/a |
95.5 % |
| Consumption in standby (night) |
< 15 W |
< 15 W |
| Consumption during operation |
65 W |
65 W |
| Cooling |
Controlled forced ventilation, variable speed fan |
Controlled forced ventilation, variable speed fan |
| Enclosure Type |
Type 3R, Powder Coated Aluminum Enclosure (standard) |
Type 3R, Powder Coated Aluminum Enclosure (standard) |
| Unit Dimensions (w/socket) (W x H x D) |
43.5 x 76.6 x 31.4 inch |
43.5 x 76.6 x 31.4 inch |
| Inverter Weight (w/socket) |
661 lbs |
661 lbs |
| Admissible Ambient Temperature |
-13 ... 122°F |
-13 ... 122°F |
| Rel. Humidity |
0 ... 95 % (non condensing) |
0 ... 95 % (non condensing) |
| AC- & DC-Disconnects |
integrated |
integrated |
| Compliance |
UL 1741-2005, IEEE 1547-2003, IEEE 1547.1,
ANSI/IEEE C62.41, FCC Part 15 B, NEC Article 690, C22. 2 No. 107.1-01 (September 2001), California Solar Initiative - Program Handbook - Appendix C: Inverter Integral 5 % Meter Performance Specification |
UL 1741-2005, IEEE 1547-2003, IEEE 1547.1,
ANSI/IEEE C62.41, FCC Part 15 B, NEC Article 690, C22. 2 No. 107.1-01 (September 2001), California Solar Initiative - Program Handbook - Appendix C: Inverter Integral 5 % Meter Performance Specification |
PROTECTION
DEVICES |
|
|
| Ground fault protection |
internal GFDI (Ground Fault Detector/Interruptor); in accordance with UL 1741-2005 and NEC Art. 690 |
internal GFDI (Ground Fault Detector/Interruptor); in accordance with UL 1741-2005 and NEC Art. 690 |
| DC reverse polarity protection |
internal diode |
internal diode |
| Islanding protection |
internal; in accordance with UL 1741-2005, IEEE 1547-2003 and NEC |
internal; in accordance with UL 1741-2005, IEEE 1547-2003 and NEC |
| Over temperature |
output power derating/active cooling |
output power derating/active cooling |